Product Detail

 

1.    Terminal block                        2.    Base                      3.    Brake magnet           4.    Frame

5.    Voltage element                       6.    Upper bearing         7.    Register                   8.    Rotor

9.    Non-reverse runing device       10. Lower bearing          11. Current element         12. Name plate

13. Cover                                     14. Terminal cove           A1. Full load adjustment (100%)

A2. Low load adjustment (5% and 10%)                              A3.Inductive load adjustment (cosф)

 

 

Data

Unit

Description

1

Type

 

CV130, CV130m, CV130mr, CV131, CV131m, CV131r, CV131mr

2

Applied standard

 

IEC60521; TCVN5411-91;ĐLVN07:2003

3

Rated voltage U­­n

V

110;120;220;230;240

4

Rated frequency fn

Hz

50 or 60

5

Rated current Ib

A

3

5

10

30

40

6

Maximum current Imax

A

9

15

30

90

120

7

Meter constant

Rev/kWh

1750

900

450

250

100

8

Rated speed at Ib

10-4Nm

3.8

3.5

3.8

4

4

9

Rated torque at Ib

Rev/min

19.25

16.5

16.5

18.33

14.66

10

Load capacity in % of Ib

Metering

300

Thermal

400

Short circuit

Current impulse peak value of 25 Imax and greater than 50 Imax­ during 1ms

11

Class

 

1

2

12

Starting current

A

0.4% Ib

0.5% Ib

13

Test of no-load condition

 

0.8 - 1.1 Un

14

Temperature coefficient between -5­­­oC and 45 oC from 0.1 Ib to Imax

Cosφ =1

%/oC

Cosφ =0.5

± 0.05

± 0.1

15

Voltage dependency between 0.9 and 1.1 1 Unat 0.5 Imax

Cosφ =1

%

Cosφ =0.5

± 0.7

± 1

± 1

± 1.5

16

Frequency dependency between 0.95 and 1.05 fn at 0.5 Imax 

Cosφ =1

%

Cosφ =0.5

± 1.3

± 1.5

17

Power consumption in votage circuit at 50Hz at Un

W/VA

1.0/4.0

18

Power consumption in current circuit at 50Hz at Ib 

VA

0.4

0.5

0.4

0.4

0.3

19

Insulation test AC for 1 minute at 50Hz

kV

2

20

Impulse voltage test 1.2/50μs

kV

6

21

Weight of roto: Jewel-magnetic floating bearing

g

20.3-22.2

22

Lower bearing

 

Jewel or magnetic floating lower bearing

23

Register

 

Normal register or Uni-directional register

24

Cover

 

Glass or PC

25

Diameter of bore in terminal

mm

8

8

8

8(11)

26

Cover of terminal

 

Extended or short terminal

27

Connection space inside extended terminal cover

mm

40

28

Degree of protection

IEC 60529

IP5X

29

Weight of meter - Plastic cover (Glass Cover)

kg

1.6

(1.9)

1.6

(1.9)

1.6

(1.9)

1.65

(1.95)

 

 

Allied Companies

  • EMIC
  • HEM
  • CADIVI
  • CTBT
  • THIBIDI
  • EPT
  • VIHEM
  • VINAKIP
  • CFT
  • HPMC