Product Detail

 

N0
 Technical characteristics 
Unit
Requirement
1
Manufactor
 
CADIVI
2
Country
 
Vietnam
3
Manufacter’s code
 
Ex: CADIVI 200… LVABC – 3x (SIZE) – 0,6/1kV
4
Standards of factory and test
 
AS 3560 or TCVN 6447 
5
Standards of quality management
 
ISO 9001-2000
6
Origin of material is used for manufacture
 
 Imported
7
Type
-
Self-supported type , the phase and neutral cores have the same cross-sectional area 
8
Insulation
-
XLPE
9
Form of conductor
-
Circular compacted , concentric stranding
10
Material
-
Alluminium with minimum tensile stress is 140 Mpa
11
Nominal of conductor
mm2
16
25
35
50
70
95
120
150
12
No of cores
core
2
2
2
2
2
2
2
2
13
No of wure in conductor
wure
7
7
7
7
19*
19*
19*
19*
14
Diameter of wire
mm
1,73
2,17
2,56
2,99
2,17
2,56
2,84
3,25
15
RDCmax of conductor at 20oC
W/km
1,91
1,20
0,868
0,641
0,443
0,320
0,253
0,206
16
RACmax of conductor at 20oC
W/km
2,37
1,49
1,08
0,796
0,551
0,398
0,315
0,257
17
Current intensity permit 
A
96
125
155
185
220
267
309
340
18
Diameter conductor
                -    (min)
                -    (max)
 
 
mm
mm
 
4,5
4,8
 
5,8
6,1
 
6,8
7,2
 
8,0
8,4
 
9,6
10,1
 
11,3
11,9
 
12,8
13,5
 
14,1
14,9
19
Maximum diameter of core (excluding ribs)
mm
7,9
9,2
10,3
11,9
13,6
15,9
17,5
18,9
20
Maximum diameter of circmscribing circle over laid-up cores
mm
15,8
18,4
20,6
23,8
27,2
31,8
35,0
37,8
21
Minium thickness of insulation
mm
1,07
1,07
1,07
1,25
1,25
1,43
1,43
1,43
22
Minium average thickness of insulation
mm
1,3
1,3
1,3
1,5
1,5
1,7
1,7
1,7
23
Maximum thickness of insulation
mm
1,9
1,9
1,9
2,1
2,1
2,3
2,3
2,3
24
Minimum bending radius of cable
mm
95
110
125
145
163
190
210
227
25
Minimum breaking load of conductor
kN
2,2
3,5
4,9
7,0
9,8
13,3
16,8
21,0
26
Minimum breaking load (MBL) of cable
kN
4,4
7,0
9,8
14,0
19,6
26,6
33,6
42,0
27
Highest value for maximum working tension (28%MBL)
kN
1,23
1,96
2,74
3,92
5,49
7,45
9,41
11,76
28
Highest value for everyday tension (18%MBL)
kN
0,79
1,26
1,76
2,52
3,53
4,79
6,04
7,56
29
Minimum load for adhesion of insulation
kg
-
-
-
100
140
190
240
300
30
Approximate mass of cable
kg/km
140
200
260
360
490
674
814
1037
31
Length of drum
m
1500
1500
1500
1500
1000
1000
500
500
32
Size of drum
No
11b
12c
13b
14c
14b
16b
13b
14a
 
 

Allied Companies

  • EMIC
  • HEM
  • CADIVI
  • CTBT
  • THIBIDI
  • EPT
  • VIHEM
  • VINAKIP
  • CFT
  • HPMC