Product Detail

 

N0

Technical characteristics

Unit

Requirement

1

Manufactor

 

CADIVI

2

Country

 

 Vietnam

3

Manufacter’s code

 

Ex: CADIVI 200… -LVABC - 4x70 - 0,6/1kV

4

Standards of factory and test

 

AS 3560 or TCVN 6447 

5

Standards of quality management

 

ISO 9001-2000

6

Origin of material is used for manufacture

 

Imported

7

Type

-

 Self- supported type :phase and neutral cores have the same cross-sectional area

8

Insulation

-

XLPE

9

Form of conductor

-

  Gircular  compacted , concentric stranding

10

Material

-

 Alluminium with minimum tensile stress is 140 Mpa

11

Nominal of conductor

mm2

16

25

35

50

70

95

120

150

12

No of cores

Core

4

4

4

4

4

4

4

4

13

No of wire in conductor

wire

7

7

7

7

19*

19*

19*

19*

14

Diameterof wire

mm

1,73

2,17

2,56

2,99

2,17

2,56

2,84

3,25

15

RDCmaxof conductor at 20oC

W/km

1,91

1,20

0,868

0,641

0,443

0,320

0,253

0,206

16

RACmaxof conductor at 20oC

W/km

   2ø,37

1,49

1,08

0,796

0,551

0,398

0,315

0,257

17

Current intensity permit 

A

78

105

125

150

185

225

260

285

18

Diameterconductor

                - min

                - max

 

mm

mm

 

4,5

4,8

 

5,8

6,1

 

6,8

7,2

 

8,0

8,4

 

9,6

10,1

 

11,3

11,9

 

12,8

13,5

 

14,1

14,9

19

Maximum diameter of core  (excluding ribs)

 

mm

7,9

9,2

10,3

11,9

13,6

15,9

17,5

18,9

20

Maximum diameter of circmscribing circle over laid-up cores

mm

19,1

22,2

24,9

28,7

32,8

38,4

42,2

45,6

21

Minium thickness of insulation

mm

1,07

1,07

1,07

1,25

1,25

1,43

1,43

1,43

22

Minium average thickness of insulation

mm

1,3

1,3

1,3

1,5

1,5

1,7

1,7

1,7

23

Maximum thickness of insulation

mm

1,9

1,9

1,9

2,1

2,1

2,3

2,3

2,3

24

Minimum bending radius of cable

mm

115

135

150

160

285

345

380

410

25

Minimum breaking load of conductor

KN

2,2

3,5

4,9

7,0

9,8

13,3

16,8

21,0

26

Minimum breaking load (MBL) of cable

KN

8,8

14,0

19,6

28,0

39,2

53,2

67,2

84

27

Highest value for maximum working tension (28%MBL)

kN

2,46

3,92

5,49

7,84

11,0

14,9

18,8

23,5

28

Highest value for everyday tension (18%MBL

kN

1,58

2,52

3,53

5,00

7,10

9,60

12,1

15,1

29

Minimum load for adhesion of insulation

kg

-

-

-

100

140

190

240

300

30

Approximate mass of cable

kg/km

275

400

529

721

981

1348

1628

2074

31

Length of cable on drum

m

1000

1000

1000

1000

1000

500

500

500

32

Size of drum

No.

11

12a

13b

14c

17

14b

16a

17

 

Allied Companies

  • EMIC
  • HEM
  • CADIVI
  • CTBT
  • THIBIDI
  • EPT
  • VIHEM
  • VINAKIP
  • CFT
  • HPMC