Product Detail

 

Specifications  

               

Type

CT0.6 (Rated voltage ≤ 600V)

CT1 (Rated voltage 720 ÷ 1000V)

Measuring accuracy class 0.5 or 1
Rated voltage (Umax) 1.2kV
Rated frequency (fn) 50Hz
Rated burden 5 ÷ 30VA
Primary rated current (In) 250 ÷ 6000A
Secondary rated current (Ib) 5A or 1A
Rated short time withstand current (Ith) 60 ÷ 80 In/s
Rated dynamic current (Idyn) 2.5 Ith
Insulation test 3kV/min
Impulse voltage test 6kV
Continous overload current 1.2 In
Operating temperature 0 ÷ 450C
Limit of temperature rise 600C
Ambient relative humidity 95%

 

Outer dimensions and Connection diagram

        

 

Technical Data

 

Rated Primary current (A) Primary number Rated burden (VA) Class Size (mm) Weight (Kg)
Diameter Length Width High Putting
D L W H A
250-500 1 5; 10 0.5; 1 50 110 56 150 100 1.5
300-600 1 5; 10 0.5; 1 50 110 56 190 100 1.5
300-600 1 5; 10 0.5; 1 80 170 56 200 120 2.8
400-800 1 5; 10 0.5 80 170 56 200 120 2.8
500-1000 1 5; 10 0.5 80 170 56 200 120 2.8
600-1200 1 5; 10 0.5 80 170 56 200 120 2.8
750-1500 1 5; 10; 20 0.5; 1 80 170 56 200 120 2.8
800-1600 1 5; 10; 20 0.5; 1 80 170 56 200 120 2.8
1000-1500 1 5; 10; 20 0.5; 1 80 170 56 200 120 3.0
1000-1500 1 5; 10; 20 0.5; 1 110 195 56 235 120 3.3
1000-2000 1 5; 10; 20; 30 0.5; 1 110 195 56 235 120 3.3
1500-3000 1 5; 10; 20; 30 0.5; 1 110 195 56 235 120 3.3
1500-3000 1 5; 10; 20; 30 0.5; 1 125 230 56 265 160 4.3
2000-4000 1 5; 10; 20; 30 0.5; 1 125 230 56 265 160 4.5
2500-5000 1 5; 10; 20; 30 0.5; 1 125 230 56 265 160 4.5

 

Allied Companies

  • EMIC
  • HEM
  • CADIVI
  • CTBT
  • THIBIDI
  • EPT
  • VIHEM
  • VINAKIP
  • CFT
  • HPMC